Intelligent electrical installation
Printed from INELS web on 09-09-2010

External master bus MI2-02M

Module MI2-02M enables to connect more units to central unit CU2-01M.

obrazek 1

  • This module manages service and control of up to 64 units and data trasmission to a central unit.
  • You can connect up to 2 modules MI2-02M to one central unit. Connection is done by communication bus TCL2.
  • Address is set by a rotary switch on a module.
  • This address must be unique in TCL2 bus.
  • It is possible to connect up to two CIB buses to MI2-02M. Each bus can carry up to 32 units of any type.
  • Maximal length of lead in the frame of one bus is 550 m with any topology.
  • Bus TCL2 can be maximally 300 m long (metallic cable – twisted pair). Regulations for bus RS-485 apply (line topology).
  • The module is supplied directly from CIB1 bus.
  • In order to supply CIB bus, it is necessary to use bus separator BPS2-02M (BPS2-01M).
  • Signalization of state for each bus (operation, error) is signalized by two-colored LED which is located on affront panel.
  • MI2-02M in 1-MODULE housing is designed for mounting into a switchboard, onto a DIN rail EN60715.